A guard is a statement about what cannot happen, and it is only true if it is tested

Interlock testing at handover is the cheapest hour in a machine's safety life, and the one most often spent on a signature instead.

Interlock testing at handover is the cheapest hour in a machine's safety life, and
07 · Interlock · First Run Notes

The difference between a guard and a barrier

A barrier is a physical object that keeps a body away from a hazard. A guard is a barrier plus a logic, and the logic is the part that decides whether the barrier is present. A barrier without logic is a fence that can be opened, and a fence that can be opened is not a safeguard, it is a suggestion.

The logic has three parts and all three are testable. Detection, which is the switch or the light curtain that knows the guard's state. Processing, which is the safety circuit that decides what the state means. Action, which is the removal of motion energy before a person can reach the hazard.

Machines are commonly delivered with detection and processing in good order, and with action that has never been measured. The measurement is a stop time, and a stop time that has never been measured is an assumption in a document that says the machine is safe.

The reason this matters at handover rather than later is that the stop time belongs to a specific configuration: a specific load, a specific speed, a specific brake condition. Once the machine is in production, that configuration changes, and the number that was never taken cannot be taken retrospectively.

Risk assessment is an input, not paperwork

A risk assessment produces three things that the hardware depends on: the hazards, the required performance level of the safety functions, and the safe distances. Each of those is a number or a category, and each is traceable to a clause.

The common defect is an assessment written after the machine was designed, to describe what was built. Such an assessment is a record of a decision that has already been made, and it will not question the guard's position or the interlock's architecture.

The practical test of an assessment is whether it could have produced a different machine. If every finding's control is exactly what the drawing shows, the assessment did not drive the design, it followed it.

At handover, the useful question is narrower: does the machine as built meet the performance level the assessment claimed. That question has an answer, and the answer is a test rather than an opinion.

Interlock architecture and what redundancy buys

A single channel interlock fails to danger when its switch sticks closed. A two channel interlock with diversity fails to danger only when both channels fail in the same way at the same time, which is a much rarer event and a much harder one to bring about by accident.

Redundancy buys failure tolerance and costs diagnostics. Two channels must be monitored, because two channels that disagree are a fault that must be detected rather than a state that must be obeyed. The monitoring is what turns redundancy into a safety function rather than a duplication.

The architecture also decides what happens after a fault. A system that latches requires a deliberate reset, which is safer and slower. A system that self resets removes the fault's visibility, and a fault that is invisible will be found again at a worse moment.

For a handover test, the architecture determines what can be tested. A monitored two channel system can be tested by defeating one channel and confirming that the system refuses to run. A single channel system can only be tested by defeating it entirely, which is a test of the guard and not of the architecture.

The stop time measurement nobody wants to take

Stop time is measured with a device that starts timing when the safety signal drops and stops when the hazardous motion has actually ceased. The second event is detected by a transducer on the moving part, not by the controller's own signal, because the controller's signal stops when the controller decides, not when the mass stops.

The measurement must be taken at the worst case. The heaviest load, the highest speed, the most adverse brake condition, and the coldest or hottest state that the machine will see in service. A stop time measured at no load and low speed is a number that describes a machine that will not exist.

The result is a number in milliseconds, and that number is the input to a distance calculation. It is also a number that changes with wear, so it belongs in the maintenance plan as a periodic check rather than in the commissioning file as a curiosity.

Three measurements are worth taking: the safety circuit's response, the drive's deceleration, and the total. A total that is much larger than the sum indicates a valve or a brake that is slow, and that component is the one to watch.

Safe distance is arithmetic, not a table

The minimum distance between a detection zone and the nearest hazard is calculated from the approach speed, the total stop time and a constant that accounts for the detection zone's depth and the body's reach. The arithmetic is standardised, and the inputs are the machine's own numbers.

The approach speed assumption is deliberately conservative, because a person reaching toward a hazard moves faster than a person walking. A table copied from another machine usually carries another machine's stop time, and a stop time is the dominant term.

The calculation's output is a distance that must be greater than or equal to the computed value, measured from the detection plane to the hazard, along the path a body would take. Measuring that distance on the installed machine, with a tape, is a five minute job that is frequently not done.

Where the computed distance exceeds the space available, the choices are to reduce the stop time or to add a physical barrier. A light curtain moved closer because the layout demanded it is a light curtain that no longer protects, and the layout is not a safety argument.

Reset, restart and the difference that kills

Reset restores the safety circuit after a demand. Restart initiates motion. These are two functions and they must not be the same button, because a person who resets a guard is not necessarily a person who has confirmed that the hazard zone is clear.

The dangerous configuration is a system in which closing the guard both resets and restarts. In that configuration, a person who closes the guard from inside the zone can start the machine while still inside it, and the guard's closure is the only evidence the system has.

The correct arrangement is a separate reset that is outside the hazard zone and that has a clear view of it, followed by a deliberate start command. The reset must be manual, must not be automatic on guard closure, and must not be reachable from inside the guarded space.

Testing this at handover is straightforward and should be done with the machine de-energised for motion. Confirm that closing the guard does not start anything, that the reset does not start anything, and that only the start command does.

Muting, blanking and the logic that defeats them

Muting is the temporary suspension of a detection function to allow material to pass without stopping the machine. It is legitimate when it is done with a defined sequence and a defined time window, and it is illegitimate when it is done with a single sensor and a timer.

A properly muted system uses several sensors arranged so that the material's passage produces a specific sequence, and so that a person's passage cannot produce the same sequence. The sequence is the safety property, not the sensors.

Blanking is the permanent disabling of part of a detection zone, used where a fixture obstructs the field. It is legitimate when the blanked area cannot admit a body, and it becomes a hazard when the blanked area grows to accommodate a change of product.

Both features are common causes of a machine that passes its handover test and fails an audit a year later, because the test was performed with the muting disabled and the production run uses it enabled. The handover test must be performed in the configuration that production will use.

Testing at handover, and the record it leaves

A handover test is a sequence of deliberate defeats, each followed by an observation. Open the guard, watch the motion stop. Defeat one channel, watch the system refuse to run. Trigger the emergency stop, watch the reset required. Each defeat is a line in the record.

The record should name the function, the method of defeat, the expected result and the observed result, with the time and the person. A record of this shape can be audited. A record that says the safety functions were verified cannot.

The tests should also be performed at the machine's slowest and fastest settings, because some safety functions depend on speed. A guard interlock that behaves correctly at low speed and fails to stop the motion at rate is a common finding on machines with mechanical braking.

The last item in the record is the stop time figure and the safe distance measured on the machine. Those two numbers together are the evidence that the geometry matches the arithmetic, and they are the numbers an inspector will ask for first.

Change control and the guard removed on a Friday

Most safety failures in service are not failures of components, they are changes made to keep production running. A guard removed to clear a jam, a interlock bypassed to test a sensor, a light curtain moved to fit a larger product. Each is a small decision made under pressure.

The defence is not discipline alone, it is a physical and procedural barrier to change. Keys for bypass, permits for modifications, and a log that makes a bypassed function visible on the line rather than in a drawer.

The second defence is a periodic re-test at an interval short enough that a change cannot survive long. A quarterly test that repeats the handover sequence will find a removed guard within a quarter, and a quarter is shorter than most audit cycles.

The third defence is the re-assessment. Any change to the machine's speed, its tooling or its product should trigger a review of the stop time and the safe distance, because both are functions of those variables and neither is a constant.

The detection, processing and action split used here is the same split machine guarding and safety systems applies when it decides what a guard has to prove.

Checkpoints12
  • The guard's detection, processing and action are each tested as separate functions.
  • Stop time is measured with a transducer on the moving part, not from the controller signal.
  • Stop time is measured at the worst case of load, speed and brake condition.
  • Safety circuit response, drive deceleration and total stop time are recorded separately.
  • Safe distance is computed from the measured stop time and verified with a tape on the machine.
  • Where the distance cannot be achieved, a physical barrier is added rather than a compromise.
  • Closing the guard does not reset and does not restart, verified with motion de-energised.
  • Reset is manual, outside the hazard zone, and has a clear view of it.
  • One channel of a two channel interlock is defeated, and the system refuses to run.
  • Muting and blanking are tested in the configuration production will actually use.
  • The handover record names each defeat, its expected result and its observed result.
  • Any change of speed, tooling or product triggers a review of stop time and safe distance.